Flying Shear Breakdown Steel processing (Siemens S5, SIEMENS STEP5)

Every 5/7 years we get called to resolve a problem on this flying shear. A pretty impressive piece of kit when it’s working.

On this occasion, the Customer was experiencing a failure to reference which was eventually traced to a “weak” Z pulse at approx 12 volts when as a minimum you need 18v ( the upper switching threshold of the computer input.

Programmed Software Siemens STEP5

Control System/Programmable Logic Controller (PLC) – Siemens S5